Appendix F: Duct-Test Recording Forms

Total Duct Leakage Test Form

Test date: _______________/20____

Fan Model _____________________Fan Serial # ___________ Digital Gauge Serial # ____________

Address: _______________________ Contact: ________________ Phone: ____________________

Technician: ________________________________________________

Step

More details and check off

1

Position DucTester near return

Ensure the flex will reach the return grill

2

Turn Air-handler off (if installed)

Put your car keys beside the switch so you remember to turn back
on

3

Remove the furnace filter and cover filter opening

4

Attach flex to return register or access door in the air
handler

Attached to __ return register, __access door

6

Seal all registers

7

Insert blue tube in a supply register

__ attached to register closest to plenum

8

Open interior and one exterior door

To make indoor and outdoor pressure the same

9

Make connections to the DucTester

__ yellow tube, __green tube, __ power cord, __ speed control

10

Connect tubes and speed control to the gauge

__ blue tube, __ yellow tube, __green tube,___ speed control

11

Enter conditioned floor area of the house into gauge

_____________ sq ft conditioned floor area

12

Create a 25 Pa pressure in the ducts

Press [Set Pressure], [25], and [Enter]. Press [@] to display “@ 25
Pa”

13

Range Configuration, usually it will be Range 74

______

14

Record Pressure (PrA) and Flow
Record Flow with @ 25 Pa displayed.
Record n and Time Avg displayed.

______ Pa ______ CFM with NO @ 25
______ CFM @ 25
___ n and ___ seconds of Time Average displayed.

15

Record Flow Direction

___ flow into ducts, __ out of the ducts

16

Record CFM/100 sq ft

_______ CFM/100 sq ft

17

Maximum Allowable duct leakage
__Post Construction: 12 CFM/100 sq ft
__Rough in Air handler installed: 6 CFM/100 sq ft
__Rough in Air handler not installed: 4 CFM/100 sq ft

___ Pass, ___ Fail.

18

Remove tape, turn HVAC equipment back ON

Return home to state you found it in

Recording form based on IECC 2009