©Retrotec Inc. 2014

20. With DucTester fan off, set the Blower Door to 25 Pa by pressing [Set Pressure] [25] [Enter] on

the Blower Door gauge.

Figure 30: Method #2: Duct Leakage to Outdoors, under depressurization

21. Press [@] if required to remove extrapolation; “@ is Off” should then be displayed on the DucTester

gauge.

22. Set the DucTester to 0 Pa by pressing [Set Pressure] [0] [Set] on DucTester gauge.
23. When 0 Pa +/– 1 is achieved on the DucTester gauge, record “Flow” from the DucTester gauge, which

is Duct Leakage to Outdoors.

Figure 31: Method #2 Duct Leakage to Outdoors, under pressurization

8.3

Duct Leakage to Outdoors with 1 gauge and 2 fans