Make sure the device shown on the Home
screen matches your fan. To change device, tap
the fan picture, then the [Change Device] key.

Select your device from the pictures, then
choose the Range.

Use Range Ring B for most houses, try “C8” for tighter
new houses, or “A” for leakier older houses.
For 300 fans, start with Open Range.

Tap on [Channel B] to change the type of result
or units. Check the Door Fan Operation Manual
to see the results required for your region.

Tap [Settings] then [Time averaging] to adjust
the time averaging. 5 seconds is OK for a calm
day. 10 or 30 seconds can be used on windy
days.

Tap [Settings] then .

Make sure the [Default @ Pressure] is set to
50 Pa.

Make sure “n” value is set to 0.65 for House.

Tap to return to the Home screen.

Step 4:

Desired results not achieved?

Cannot achieve test pressure at full speed?

If fan reaches 100% speed before reaching 50 Pa:

Check to see if all doors and windows are closed.

Remove a Range Ring and try again.

Change [Range] on the gauge to match.

Re-adjust fan speed.

Tap [@ Pressure] to get the gauge to calculate

what the flow would be at exactly 50 Pa.

Flow reads “--” at test pressure?

If the test pressure has been reached, but “--” appears, the fan
is running too slowly to accurately measure flow.

Add the next lower Range

Change [Range] to match

Gauge set up

Press [On] to power up the gauge.

Tap [Settings] then [Baseline].

Tap [Capture Baseline] and 20 seconds on a calm day or

60 seconds on a windy day, then tap [End Capture] then
[On] to return to the Home screen.

Uncover fan. Install Range Ring B (Open for 300 fan).

Make sure gauge shows the correct Range on Home screen.

Step 3:

Conduct depressurization

test, (CFM@50)

Disconnect Speed Control Cable, then adjust Speed

Control knob until pressure is about 50 Pa.

Page 2 of 4

2520

Tap [@ Pressure] to extrapolate results to exactly 50 Pa.

Record results.

Open