Retrotec 5000 Blower Door with DM32 User Manual
Dm32 blower door quickguide
Water in the tube will result in erroneous readings.
DM32 Blower Door QuickGuide
Step 1:
Prepare the building
Refer to the Gauge QuickGuide and become completely
familiar with its operation before performing a test.
□
Fireplaces and stoves must be cold with doors
closed (cover ashes).
□
Close and lock outside doors and windows so they
don’t open during the test.
□
Open all interior doors leading to conditioned spaces.
□
Shut off HVAC, combustion appliances, exhaust fans,
dryers, A/C and furnaces. Ensure they will not come on
□
Turn gas hot water to Pilot.
□ Set up the Door Panel.
Refer to your “Door Panel QuickGuide”
□ Connect the short red tube to the red port on the
gauge.
□ Connect the yellow tube between yellow ports marked
“Ref B” on fan and gauge. If the fan has a green port
(“Input B”), connect the green tube.
□ Connect the Ethernet style Speed Control Cable to the
fan and gauge.
□ Pass the red tube through the Door Panel and toss
the end at least 5 feet away from the fan’s airstream.
Remove or cover
ashes.
Turn gas valve
to Pilot.
Close all windows
and outside doors.
□
Place gauge near fan, or attach gauge to Door Panel.
□
Install the fan blowing outdoors. Cover the fan.
□
Connect power cord between fan and a wall outlet.
Power light must be on.
Step 2:
Install the system
QG303 Page 1 of 4 rev-2015-05-12
www.retrotec.com Support: (888)330-1345 International: +1(604)732-0142 Made in Everson, WA USA
DM32 digital gauge
Cloth panel
Download the “Blower Door Operation Manual” and the
“Residential Pressure & Air Leakage Testing Manual” from
www.retrotec.com Read warnings.