Retrotec Blower Door with DM-2 User Manual
Quickguide, Blower door
Water in the tube will result in erroneous readings.
QuickGuide
Blower Door
Step 1:
Prepare the building
□
Close outside doors and windows.
□
Open all interior doors leading to conditioned spaces.
□
Turn gas, hot water, to Pilot.
□
Fireplaces and stoves must be cold with doors
closed (cover ashes).
□
Shut off HVAC, combustion appliances, exhaust fans,
dryers, A/C and furnaces.
See: Manual-Residential Pressure & Air Leakage Testing for
additional information.
□
Set up the Door Panel.
See: DoorPanel-Cloth or DoorPanel-Modular QuickGuide
□
Connect the yellow tube between yellow ports
marked “Ref B” on fan and DM-2. If the fan has a
green port (“Input B”), connect the green tube.
□
Connect the Speed Control Cable from fan to gauge.
Do not connect to the Internet!
□
Pass long red tube through the Door Panel and toss
the end at least 5 feet away from the fan’s airstream.
Remove or cover
ashes.
Turn gas valve
to Pilot.
Close all windows
and outside doors.
Place gauge case near fan, or attach gauge to Door Panel.
□
Install the fan blowing outdoors. Cover fan.
□
Connect the fan power plug to a wall outlet.
1000
Device=”Retrotec 1000”
Q46, Q56
Device= “Retrotec 2000”
Q4E, Q5E, QMG
Device= “Retrotec 3000SR”
Step 2:
Install the system
QG300 Page 1 of 4 rev-2012-08-29