beautypg.com

10 digital input connection (di), 11 use of an external relay, 9 relay output connection (relay) – Precision Digital PD540 User Manual

Page 54

background image

Switching Inductive Loads

When using switching in ductive loads, the use of RC networks (snubbers) for AC loads or diodes for DC loads is
recommended to prevent disrupting the microprocessor's operation. The suppressors also prolong the life of the
relay contacts. Suppression can be obtained with resistor-capacitor (RC) networks or diodes assembled by the
user or purchased as complete assemblies.
For AC loads, choose R and C as follows:
R: 0.5 to 1

Ω for each volt across the contact

C: 0.5 to 1

μF for each amp through closed contacts

Notes:
1. Use capacitors rated for 250 VAC.
2. RC networks may affect load release time of solenoid loads. Check to confirm proper operation.
3. RC networks are available from Precision Digital and should be applied to each relay contact switching an

inductive load. Part number: PDX6901.

If the load inductance is over the controller specifications, the output may need a RC filter (snubber) or
diode to properly handle frequent relay switching operations.

To prevent electric shock, be sure to turn off power to the Nova Controller and the source circuit breaker
before wiring.

To prevent electric shock, be sure to turn off power to the Nova Controller and the source circuit breaker
before wiring.

7.10 Digital Input Connection (DI)

!

CAUTION

„ Use a no-voltage contact switch such as relay.
„ The controller supplies the need ed voltage (approx. 5 VDC) and current (approx. 1 mA) to trigger the input.
„ When using an Open Collector (TR) as a trigger, use one with a 2 V or lower voltage rating when "on" and
100

μA or less leakage current when it is OFF.

7.11 Use of an External Relay

!

CAUTION

DI_2

NOVA

DI_COM

DI_1

Relay Contact Connection

DI_2

NOVA

DI_COM

DI_1

+5V

Transistor Contact Connection

7.9 Relay Output Connection (RELAY)

!

CAUTION

COM

NOVA

Relay: NC - Normally Closed Connection

Relay: NO - Normally Open Connection

PD540 Series Nova Digital Process and Temperature Controller

Instruction Manual

54

This manual is related to the following products: