Alm1 ret heat alm2 alm3 ssr – Precision Digital PD540 User Manual
Page 19
?
NOTE
5.2 Output Group (G.OUT)
Press SET/ENT key to select input group. (Refer to parameter map in section 3.)
This parameter sets the type of operation for output 1. (OUT1: relay output)
The output can be set to HEAT, COOL, ALM1, ALM2, ALM3, or RUN. Its default setting is
ALM1. (COOL is displayed on H/C models only. Skip when ON/OFF Mode selected.)
This parameter establishes the type of operation for output 2. (OUT2: 4-20 mA or voltage
pulse) Settings can be HEAT, COOL, or RET (retransmitting). Its default setting is
HEAT. (COOL is displayed on H/C models only.)
This parameter establishes the type of operation for output 3. (OUT3: 4-20 mA or voltage
pulse) Settings can be HEAT, COOL, or RET (retransmitting). Its default setting is
HEAT. (COOL is displayed on H/C models only.) Valid for models with OUT3 only.
This parameter selects the type of output signal for each analog output (OUT2 and OUT3)
when they are set to HEAT. The outputs can be set to SSR (pulse output) or
SCR (4-20 mA). Its default setting is SSR.
PV
PV
PV
PV
This parameter sets the type of operation for auxiliary output 1 (SUB1: relay output)
Output can be set to HEAT, COOL, ALM1, ALM2, ALM3, or RUN. Its default setting is
ALM2. (COOL is displayed on H/C models only. Menu appears only on models with the
SUB1 output option.)
This parameter sets the type of operation for auxiliary output 2 (SUB2: relay output)
Output can be set to HEAT, COOL, ALM1, ALM2, ALM3, or RUN. Its default setting is
ALM2. (COOL is displayed on H/C models only. Menu appears only on models with the
SUB2 output option.)
PV
PV
Output Group Menu Progression Example:
The following settings establish relay out put 1 (OUT1) to trigger based on alarm 1, for analog output 2 (OUT2) to
operate as a heating tem perature controller outputting a voltage pulse, for analog output 3 (OUT 3) to output a
retransmitting 4-20 mA s ignal, and for auxiliary relay outputs SUB1 and SUB2 to trigger with alarm 2 and alarm 3.
PV
SP
PV
SP
PV
SP
PV
SP
PV
SP
PV
PV
SP
This parameter selects the type of output signal for each analog output (OUT2 and OUT3)
when they are set to COOL. The outputs can be set to SSR (pulse output) or SCR (4-
20mA). Its default setting is SSR.
PV
G.AT G.SP G.PID PWD G.CTL G.IN
G.COM G.RET G.ALM G.OUT
G.oUT
oUT1
oUT2
oUT3
HEAT
cooL
sUB1
SUB2
oUT1
oUT2
oUT3
HEAT
sUB1
SUB2
alm1
ret
HEAT
alm2
Alm3
ssr
PD540 Series Nova Digital Process and Temperature Controller
Instruction Manual
19