Precision Digital PD540 User Manual
Page 30
OH
(90%)
100
50
0
50
100
DB
(20%)
0
0
50
100
OL-LIMIT
(0 %)
OH-LIMIT
(105%)
OUTPUT
COOL
HEAT
HYS
Fig 8: Heating PID and Cooling On/Off Outputs
Display
Parameter
Setting Range
Unit
Default
Remarks
n.MR
n.Manual Reset
-5.0 to 105.0%
%
50.0%
Used if I=0,
or H/C Model
ARW
FUZY
PID
n.P
n.I
n.D
Anti-Reset Wind-Up
Auto or 50.0 to 200.0%
%
Auto
Fuzzy
OFF, ON
ABS
OFF
PID Number
MENU (0), 1, 2, 3, or 4
ABS
MENU
n.Proportional Band
0.1 (H/C Models:0.0) to 999.9%
%
10.0%
n.Integral Time
OFF, 1 to 6000 seconds
sec
120 sec
n.Derivative Time
OFF, 1 to 6000 seconds
sec
30 sec
n.DB
n.Deadband
-100.0 to 50.0%
%
3.0%
H/C
Models Only
n.Pc
n.Ic
n.Dc
n.Proportional Band
for Cooling Side
0.0 (ON/OFF Control) or 0.1 to 999.9%
%
10.0%
H/C
Models Only
n.Integral Time for
Cooling Side
OFF, 1 to 6000 sec
sec
120 sec
H/C
Models Only
n.Derivative Time for
Cooling Side
OFF, 1 to 6000 sec
sec
30 sec
H/C
Models Only
1.RP
Reference Point 1
AEU (0.0%), 1.RP < 2.RP
AEU
100.0%
PID Zone 1
2.RP
Reference Poin t2
1.RP < 2.RP < AEU (100.0%)
AEU
100.0%
PID Zone 2
RHY
Reference
Hysteresis
GEU (0.0 to 10.0%)
GEU
0.3%
PID Zone 3
RDV
Reference
Deviation
GEU (0.0 to 100.0%)
GEU
0.0%
PID Zone 4
PID Group Parameter Summary
C.MOD
Control Mode
Differential of Deviation Value (d. dV) or
Process Variable (d. PV)
ABS
d. dV
PD540 Series Nova Digital Process and Temperature Controller
Instruction Manual
30