G.ret ret reth retl, 8 retransmission group (g.ret) – Precision Digital PD540 User Manual
Page 36
?
NOTE
5.8 Retransmission Group (G.RET)
This parameter sets the type of retransmission operation to use. Options are PV, SP, MV,
and LPS. See notes below for an explanation of the retransmission types.
The default setting is PV.
PV
These parameters are used to scale the retransmitting output. They set the high and low
limits for th e retransmission output scale, as shown below. The retransmitting outputs will
transmit 4 mA at th e low limit (RETL) and 20 mA at the high limit (RETH) values. These
limi ts are used when the retransmission type is set to PV or SP.
RETL
4.0 mA
12.0 mA
RETH
20.0 mA
PV
PV
PV and SP Type Retransmission Scale
PV type retransmits based on the input value, SP retransmits based on the set point value.
0.0%
(No Output)
4.0 mA
12.0 mA
100.0%
(Maximum Output)
20.0 mA
MV Type Retransmission Scale
MV type retransmits based on the full scale output and what is currently being transmitted by the control outputs
Display
Parameter
Setting Range
Unit
Default
Remark
RET
RETH
RETL
Select Ret Type
PV, SP, MV, LPS
ABS
PV
Ret Scale
High Limit
T/C, RTD: INRH to INRL
mV, V: INSH to INSL
RETH > RETL
AEU
INRH
Only valid
when RET
is set to
PV or SP
Ret Scale
Low Limit
AEU
INRL
PV
Press SET/ENT key to select retransmission group. (Refer to parameter map.)
g.ret
ret
retH
retl
G.AT G.SP G.PID PWD G.CTL G.IN
G.COM G.RET G.ALM G.OUT
Retransmission Group Parameter Summary
LPS Type Retransmission
LPS (Loop Power Suppy) retransmitting outputs will transmit a 14-18 VDC @ 20 mA power supply output.
PD540 Series Nova Digital Process and Temperature Controller
Instruction Manual
36