Calibrating the Meter (Cal)

To scale the meter without a signal source refer to
Scaling the Meter (SCL), page 21.

The meter can be calibrated to display the process in engineering units by
applying the appropriate input signal and following the calibration procedure.
The use of a calibrated signal source is strongly recommended.

Press the Up arrow button to scroll to the Calibration menu (CAL) and press
Enter

.

If using linear signal input conditioning, enter the number of calibration points (2-
32).
The meter displays in1. Apply a known signal and press Enter. The display will
flash while accepting the signal.
When the meter displays d1, press Enter. Enter a corresponding display value
for the signal input, and press Enter to accept.
The meter displays in2. Apply a known signal and press Enter. The display will
flash while accepting the signal.
When the meter displays d2, press Enter. Enter a corresponding display value
for the signal input, and press Enter to accept.

Re-calibrating the Internal Calibration
Reference (
ICal)

The Internal Calibration (ICAL) menu, located in the Advanced features menu, is
used to recalibrate the internal calibration reference. Recalibration is
recommended at least every twelve months. Refer to Internal Calibration (ICal),
page 26 for instructions.

d1

Press Enter to
Accept Setting

in2

Calibrate

Input 2

in1

ENTER

Set Display 1

Value

Press Up to
Set Digit Value

Press Right to
Select Next Digit

Press Menu to
Exit at any Time

0

00.0

MENU

npt

0

0

2

Number of Points

menu

not displayed for square
root input conditioning.

Set Number of
Scale Points

Cal

Display Flashes

Accepting Input