5. SYSTEM COMPONENTS

4. INSTALLATION

4.1.

Clips and clip spacers are available to support the piping (see Section 5) and these should be used within the following parameters:
• Distance between fitting centre and clip centre should be 50cm (fig. 4)
• Distance between clip centres should be 100cm (fig. 4)
• Clip horizontal runs first (fig. 4) and then clip vertical runs with the system lightly pressurised (fig. 5). This will ensure that vertical runs are vertical.
• Long pipe runs should include an expansion loop every 25mtr (fig. 6).

fig. 4

fig. 5

fig. 6

CAS15NP 15mm x 3mtr Pipe - Pack of 5
CAS22NP 22mm x 3mtr Pipe - Pack of 5

CAS15ET 15mm Equal Tee - Pack of 5
CAS22ET 22mm Equal Tee - Pack of 5

CAS15SC 15mm Straight Connector

Pack of 5

CAS22SC 22mm Straight Connector

Pack of 5

CAS15EE 15mm Equal Elbow

Pack of 5

CAS22EE 22mm Equal Elbow

Pack of 5

CAS15STA 15mmx1/2”BSP Stem Adaptor

Pack of 2

CAS22STA 22mmx3/4”BSP Stem Adaptor

Pack of 2

CAS15SE 15mm Stem Elbow

Pack of 2

CAS22SE 22mm Stem Elbow

Pack of 2

The Sealey CAS System offers the following components:

4.2.

When routing pipe around pillars etc. gaps between the pipe and the pillar must be provided to allow for expansion, as shown in fig. 7.

fig. 7

AIR RING MAIN SYSTEM - 2 - 030305