beautypg.com

Specifications, English – Eaton Electrical 9130 User Manual

Page 33

background image

Page 33

9130 UPS-EN

ENGLISH

7. Specifications

Table 22. Environmental and Safety

Surge Suppression

EN 61000-2-2
EN 61000-4-2, Level 3
EN 61000-4-3, Level 3
EN 61000-4-4, Level 3 (also on signal ports)
EN 6100-4-5, Level 3 Criteria A (IEEE C62.41 6 KV)
EN 61000-4-6, Level 3
EN 61000-4-8, Level 4
EN 6100-4-11

EMC Certifications

CE per IEC/EN 62040-2,
Emissions: Category C2,
Immunity: Category C2

EMC (Emissions)

IEC 62040-2:ed2:2005 / EN 62040-2:2006

Safety Conformance

IEC 62040-1-1, IEC 60950-1

Agency Markings

CE

Operating Temperature

0 °C to 40 °C (32 °F to 104 °F) in Online mode, with linear derating for
altitude
NOTE: Thermal protection switches load to Bypass in case of overheating.

Storage Temperature

-20 °C to 40 °C (-4 °F to 104 °F) with batteries
-25 °C to 55 °C (-13 °F to 131 °F) without batteries

Transit Temperature

-25 °C to 55 °C (-13 °F to 131 °F)

Relative Humidity

5–90 % noncondensing

Operating Altitude

Up to 3,000 meters (9,843 ft) above sea level

Transit Altitude

Up to 10,000 meters (32,808 ft) above sea level

Audible Noise

< 55 dBA at 1 meter typical

Leakage Current

< 1.5 mA

Table 23. Battery Runtimes (in Minutes) at 100 % Load

Model

Internal Batteries

+ 1 EBM

+ 2 EBMs

+ 3 EBMs

+ 4 EBMs

PW9130i5000T-XL

9 min

41 min

1 h 19 min

1 h 57 min

2 h 42 min

PW9130i6000T-XL

6 min

32 min

1 h 03 min

1 h 37 min

2 h 08 min

Note: Battery times are approximate and vary depending on the load configuration and battery charge.

Table 24. Battery

Internal Batteries

EBMs

Tower Configuration

5000–6000 VA models: 240 Vdc
(20 12 V, 7 Ah)

PW9130N6000T-EBM: 240 Vdc
(2 x 20 12 V, 7 Ah)

Fuses

30 A* 2/600 Vdc

30 A* 2/600 Vdc fuses per EBM

Type

Sealed, maintenance-free, valve-regulated, lead-acid, with minimum 3-year
float service life at 25 °C (77 °F)

Monitoring

Advanced monitoring for earlier failure detection and warning

Recharge Time (to 90
%)

Internal batteries: 3 hours
1 EBM: 9 hours; 2 EBMs: 15 hours; 3 EBMs: 21 hours; 4 EBMs: 27 hours

Battery Port

External five-pole Banana connector on UPS for connection to EBM

EBM battery cable
length

50 cm