7. Specifications
7.1
Model Specifications
This section provides the following specifications:
Communication options
Model lists
Weights and dimensions
Electrical input and output
Environmental and safety
Battery
Table 13. Communication Options
Communication Bay
(1) available independent communication bay for connectivity cards
Compatible
Connectivity Cards
Connect UPS-MS Web/SNMP Card
Relay Interface Card
Communication Ports
RS-232 (DB-9): 1200–9600 bps
USB: 9600 bps
Signal Inputs
(4) programmable signal inputs (signal and signal return) for indicating
building alarms or other use
Relay Output Contacts
(1) three-pole connector with (1) contact closure
Table 14. Extended Battery Module Model List
EBM Model
Configuration
Battery Voltage
For Power Ratings
PW9130N6000T-EBM
Tower
240 Vdc
5000–6000 VA
Table 15. UPS Model List
Model
Power Level
Rear Panel Diagram
PW9130i5000T-XL
5000 VA / 4500 W
Figure 21 on page 21
PW9130i6000T-XL
6000 VA / 5400 W
Figure 21 on page 21
Table 16. Weights and Dimensions
Model (Tower UPS)
Dimensions (H W D)
Weight
PW9130i5000T-XL
PW9130i6000T-XL
575* 242 542 mm (22.64”* 9.53” 21,34”) 105 kg (231.5 lb)
Model (Tower EBM)
Dimensions (H W D)
Weight
PW9130N6000T-EBM
575* 242 542 mm (22.64”* 9.53” 21.34”) 120 kg (264.55 lb)
Table 17. Electrical Input
Nominal Frequency
50/60 Hz auto-sensing
Frequency Range
40–70 Hz before transfer to battery
Bypass Voltage Range
+10 / -15 % of nominal (default)
Noise Filtering
MOVs for normal and common
mode noise