5. Communication

The table 10 shows the options for the relay output contacts.
Table 10. Relay Output Configuration Options

Relay Signal

Description

UPS ok

Activated when the UPS is feeding the load on inverter or on bypass and no
alarms are active

On Bypass

Activated when the UPS is NOT on bypass operation

On Battery

Activated when the UPS operates on battery and the "On Battery Notice
Delay" time has expired

Battery Low

Activated with the "Battery Low" alarm according to the "Battery Low Alarm"
setting

Ext. Charger On

Controls an optional external battery charger on and off

The figure 25 shows the connection of the relay output contacts.

1

2

3

Figure 25. Standard Relay Port Connections.

The figure 26 shows an example where a lamp is connected on the relay output contacts.

1

3

G

2

3

G

Relay signal

L1

L2

True

Not true

G : external power supply

Figure 26. Example of Standard Relay Port Connections with lamp.

Programmable Signal Inputs

The UPS incorporates four programmable signal inputs: one RS 232 input, two connectivity card inputs,
and one RPO terminal input. See figure 21 on page 21 for the locations of the ports. Configure the
inputs with the "Signal Inputs" setting in "User Settings" on page 15.

The table 11 shows the programmable settings for the signal inputs. Table 12 shows the operation logic
for the signal inputs.
Table 11. Programmable Signal Inputs

Signal

Description

Not Used

The input operates only as a serial input (RxD) or has no function.

Force Bypass

If active, the UPS is forced to static bypass operation regardless of the bypass
status.

Remote
Shutdown

If active, the UPS output turns off after a user-defined remote shutdown delay.
The batteries continue charging. Inactive input does not abort the shutdown
countdown and does not cause the UPS to start up automatically.

Delayed
Shutdown
(and restart)

If active, the UPS output turns off after a user-defined delayed shutdown delay.
The batteries continue charging. Inactive input does not abort the shutdown
countdown but will cause the UPS to start up automatically if the input voltage
exists.

On Generator

If active, synchronization is disabled and the UPS transfers to bypass.

Building Alarm 1

If active, the UPS generates the "Building Alarm 1" alarm.

Common

Common

Common

Normally closed

Normally open

Normally
open

Normally
closed