beautypg.com

Operation, English – Eaton Electrical 9130 User Manual

Page 15

background image

Page 15

9130 UPS-EN

ENGLISH

4. Operation

The table 4 shows the basic menu structure.
Table 4. Menu Map for Display Functions

Main Menu

Submenu

Display Information or Menu Function

UPS Status

Main status (mode and load) / Notice or Alarm status
(if any) / Battery status (state and charge level)

Event Log

Displays up to 127 events and alarms.
The Event Log is also available through the serial port. See
"Retrieving the Event Log" on page 19.

Measurements

Load W VA / Load A pf / Output V Hz / Input V Hz / Bypass V Hz /
Input Line Events / Battery V min

Control

Go to Bypass

Transfers the UPS system to internal Bypass mode.
When this command is active, the option changes to "Go to
Normal".

Start Battery Test

Starts a manual battery test.
See "Testing New Batteries" on page 29.

Reset Error State

Clears a "Battery Test Failed" alarm

Restore Factory Settings

Returns all settings to original values

Identification

UPS Type / Part Number / Serial Number / Firmware

Settings

User Settings

See Table 5 for details.

Service Settings

This menu is password-protected.

User Settings

The following table displays the options that can be changed by the user.
Table 5. User Settings

Description

Available Settings

Default Setting

Change Language

[English] [French] [Spanish] [German] [Russian]
Menus, status, notices, and alarms are in all
supported languages. UPS faults, Event Log data,
and settings are in English only.

English

User Password

[Enabled] [Disabled]
If Enabled is selected, the password is USER.

Disabled

Audible Alarms

[Enabled] [Disabled]

Enabled

Set Date and Time
NOTE: time is a 24-hour
clock.

Set Year, Month, Day, Hours, Minutes
Date: yyyy/mm/dd
Time: hh:mm

2008/01/01
12:00

Signal Inputs

Setup: [Not Used] [Force Bypass] [Remote
Shutdown] [Delayed Shutdown]
[On Generator] [Building Alarm 1]
Active: [High] [Low]
See "Programmable Signal Inputs" on page 24.

RS232-3: Not Used, High
cXSlot Serial: Delayed
Shutdown, High
cXSlot Signal: Remote
Shutdown, Low

Relay Configuration

[UPS ok] [On Bypass] [On Battery] [Battery Low]
[Ext. Charger On]
See "Relay Output Contacts" on page 23.

Standard: UPS ok
RS232-1: Battery Low
RS232-8: On Battery
cXSlot-K1: On Battery
cXSlot-K2: Battery Low
cXSlot-K3: UPS ok
cXSlot-K4: On Bypass

Serial Port Configuration

[1200 bps] [2400 bps] [9600 bps]
NOTE: USB communication requires 9600 bps.

RS232: 9600 bps
cXSlot: 9600 bps

Control Commands from
Serial Port

[Enabled] [Disabled]

RS232: Enabled
cXSlot: Enabled

Output Voltage

[208V] [220V] [230V] [240V] [Autosensing]

230 V

Output Frequency

[50Hz] [60Hz] [Autosensing]

Autosensing

Frequency Converter

[Enabled] [Disabled]
If Enabled, the UPS operates as a frequency
converter, with bypass operation and all bypass-
related alarms disabled.

Disabled

Overload Alarm Level

[10%] [20%] [30%] ... [100%]
These values affect alarm level only, not UPS
operation such as transfers or shutdown.

100 %
Generates the Output.
Overload alarm at the set
level.

Transfer to Bypass When
Overload*

[Immediate] [After Delay]
If Immediate, transfer occurs at load > 102 %.
If After Delay, transfer occurs according to table 20
on page 32.

After Delay