-2-

TABLE 2

REQUIREMENTS FOR THERMAL INBREATHING - METRIC UNITS (AIR)

(Column 1)

(Column 2)

(Column 1)

(Column 2)

TANK CAPACITY

INBREATHING

TANK CAPACITY

INBREATHING

CUBIC METERS

Nm3/H

CUBIC METERS

Mn3/H

10

1.69

5000

787

20

3.37

6000

896

100

16.9

7000

1003

200

33.7

8000

1077

300

50.6

9000

1136

500

84.3

10000

1210

700

118

12000

1345

1000

169

14000

1480

1500

253

16000

1615

2000

337

18000

1745

3000

506

20000

1877

3180

536

25000

2179

4000

647

30000

2495

NOTE: Table and sizing from API 2000 fifth edition, April 1998

TABLE 1

REQUIREMENTS FOR THERMAL INBREATHING - ENGLISH UNITS (AIR)

(Column 1)

(Column 2)

(Column 1)

(Column 2)

TANK CAPACITY

INBREATHING

TANK CAPACITY

INBREATHING

Barrels

Gallons

SCFH

Barrels

Gallons

SCFH

60

2,500

60

35,000

1,470,000

31,000

100

4,200

100

40,000

1,680,000

34,000

500

21,000

500

45,000

1,890,000

37,000

1000

42,000

1000

50,000

2,100,000

40,000

2,000

84,000

2,000

60,000

2,520,000

44,000

3,000

126,000

3,000

70,000

2,940,000

48,000

4,000

168,000

4,000

80,000

3,360,000

52,000

5,000

210,000

5,000

90,000

3,780,000

56,000

10,000

420,000

10,000

100,000

4,200,000

60,000

15,000

630,000

15,000

120,000

5,040,000

68,000

20,000

840,000

20,000

140,000

5,880,000

75,000

25,000

1,050,000

24,000

160,000

6,720,000

82,000

30,000

1,260,000

28,000

180,000

7,560,000

90,000

NOTE: Table and sizing from API 2000 fifth edition, April 1998