beautypg.com

Jordan Valve Mark 6127 Series Pressure Reducing Valves User Manual

I & m mark 6127 series, Ntroduction

background image

6.

Y-Strainer

(standard on water service valves)

or Inline Strainer (standard on fuel service

valves).The strainer protects the pilot system

from solid contaminants in the line fluid.

7 A/B. Two Ball Valves (standard on water service

valves, optional on fuel service valves),

useful for isolating the pilot system for

maintenance or troubleshooting.

At user option, the Mark 6127 may also be equipped

with the following:

1.

Visual Indicator.

2.

Limit Switch Assembly (includes visual

indicator).

3.

Closing Speed Control

I

ntroductIon

The Jordan Valve Mark 6127 Pressure-Reducing/

Sustaining Valve is designed to perform the following

functions:

1.

Reduce a higher upstream pressure into a lower,

constant downstream pressure.

2.

Prevent upstream pressure from falling below

a predetermined minimum.

The 6127 consists of the following components:

1.

Main Valve

, a hydraulically-

operated, diaphragm-actuated globe or

angle valve which closes with an elastomer-on-

metal seal.

2.

Pressure-Reducing Pilot

, a two way, normally-

open pilot valve which senses downstream

pressure under its diaphragm and balances it

against an adjustable spring load. An increase

in downstream pressure tends to make the pilot

close.

3.

Pressure Sustaining Pilot

, a two way,

normally-closed pilot valve which senses

upstream pressure under its diaphragm and

balances it against an adjustable spring load.

An increase in upstream pressure tends to make

the pilot open.

4.

Ejector

, a simple "tee" fitting with a fixed orifice

in its upstream port. It provides the proper

pressure to the diaphragm chamber of the

main valve, depending on the position of the

pressure-reducing pilot.

5.

Flow Control Valve

, a needle type valve which

provides adjustable, restricted flow in one

direction and free flow in the opposite direction

On the 6127, the flow control valve is

connected as an opening speed control.

3170 Wasson Road • Cincinnati, OH 45209
Phone 513.533.5600 • Fax 513.871.0105 (f)
[email protected] • www.jordanvalve.com

I & M Mark 6127 Series

Installation & Maintenance Instructions for the

Mark 6127Pressure Regulating Valve

Warning: Jordan Valve Control Valves must only be used, installed and repaired in accordance with these Installa-
tion & Maintenance Instructions. Observe all applicable public and company codes and regulations. In the event
of leakage or other malfunction, call a qualified service person; continued operation may cause system failure or
a general hazard. Before servicing any valve, disconnect, shut off, or bypass all pressurized fluid. Before disassem-
bling a valve, be sure to release all spring tension.