Jordan Valve Mark 508 Series – Tank Blanketing Valve User Manual
Page 16

TABLE 6 TANK BLANKETING VALVE CAPACITIES 1” MARK 608BP WITH 5/16” ORIFICE
Range
Setpoint
Inlet Pressure
330Nitrogen @ 0.97sg
Deviation from Setpoint (in/water)
+/- 0.5
+/- 1.0
+/- 2.0
2 - 5.5" w.c.
4" w.c.
5
247
424
601
20
563
1408
2065
40
1119
2592
3535
60
2065
4957
5095
4 - 10" w.c.
7" w.c.
5
212
424
636
20
375
938
1689
40
589
1414
3535
60
688
3029
5095
80
1240
4341
6201
5 - 30" w.c.
20" w.c.
5
141
212
424
20
188
375
563
40
236
471
825
60
207
413
964
80
233
620
1860
100
341
853
2730
125
377
753
3013
150
446
881
3577
0.5 - 1.75 psi
1 psi
5
71
212
530
20
235
610
1689
40
412
825
2710
60
551
1033
4819
80
620
1705
6046
100
853
1877
6995
125
753
2260
8473
150
881
2642
10016
1 - 3.5 psi
3 psi
5
566
884
1273
20
657
1689
2065
40
1296
2592
3535
60
1928
4819
5095
80
2480
6201
6511
100
3242
7166
8019
125
4142
8662
9791
150
4898
10236
11556
-13-
This manual is related to the following products: