Speed command operation parameter correct setting, Speed command operation parameter is set correctly, Troubleshooting a-6 – Yaskawa E7 Apogee FLN User Manual
Page 50

Troubleshooting A-6
!
Speed Command Operation Parameter Is Set Correctly
The speed command operation parameter needs to be set for “Serial Com”.
Table A.2 - Speed Command Operation Parameter
Parameter Number
Setting Choices
Setting Descriptions
0 Operator
1 Terminals
2
Serial Com (APOGEE FLN)
b1-01
3 Option
PCB
Correct and Unique Network Address
Each device on an APOGEE FLN network requires its own unique address. The drive also needs to be programmed to accept the APOGEE
FLN protocol.
Table A.3 - Serial Communication Device Address Parameter
Parameter Number
Setting Range
Setting Description
H5-01
0 to 63 hex
Serial communication device address
H5-08
0 to 2
2: FLN (APOGEE)
This manual is related to the following products: