beautypg.com

Apogee fln set-up, Caution, Installation 1-5 – Yaskawa E7 Apogee FLN User Manual

Page 11: A1-00 = 0, B1-01 = 2

background image

Installation 1-5

APOGEE FLN Set-Up

A Yaskawa Electric America, Inc. representative is responsible for proper configuration of the drive for its primary application, while a
Siemens Building Technologies, Inc. representative is responsible for field panel programming to make use of the drive’s functionality in
the building automation system. As such, there must be coordination between the Yaskawa Electric America and Siemens Building
Technologies representatives to ensure that the programming of the drive is consistent with the particular application requirements. After
verifying that the drive installation and wiring are correct, apply power to the drive. Table 1.1 below lists the parameters and their values
required for proper APOGEE FLN communication and control.

E7 Drive Parameter Settings For APOGEE FLN Communications

Table 1.1 - Drive Communication Parameter Settings

Parameter Number

Digital Operator Display

Settings for APOGEE FLN Communication

b1-01

Reference Source

2: Serial Com

b1-02

Run Source

2: Serial Com

H5-01

Serial Comm Adr

Select the drive address (default = 1Fh (31 dec))

H5-02

Serial Baud Rate

2: 4800 Baud

H5-08

Protocol Select

2: FLN(APOGEE)

CAUTION

A YEA representative should set the drive parameters to their appropriate values. Changes made to
the parameters other than what is listed in the table above can result in damaging the drive or
building equipment.

Programming The E7 Drive For APOGEE FLN

The procedure for programming the E7 drive for communication on an APOGEE FLN network is shown in the table below: Refer to the
E7 User Manual, TM.E7.01, for detailed information on using the E7 Operator.

Table 1.2 - Drive Programming Procedure for APOGEE FLN

Description

Key Operation

Digital Operator Display

Apply Power to the drive

-DRIVE-

Rdy

Frequency Ref

U1-01 =

0.00Hz

- - - - - - - - - - - - - - - - - - - - - - - - - -

U1-02

=

0.00Hz

U1-03

=

0.00A

Select Programming Menu

Press the MENU key until the display matches

the display to the right.

x3

-ADV-

** Main Menu **

- - - - - - - - - - - - - - - - - - - - - - - - - -

Programming

Enter Programming Menu

Press the DATA ENTER key to select the
Programming Menu (A1 blinking)

-ADV-

Initialization

- - - - - - - - - - - - - - - - - - - - - - - - - -

A1-00 = 0

Select Language

Select Sequence Parameters

Press the UP ARROW key until Reference
Source
is displayed (b1 blinking).

Note: The item selected will blink.

x2

-ADV-

Sequence

- - - - - - - - - - - - - - - - - - - - - - - - - -

b1-01 = 2

Reference Source