A Yaskawa Electric America, Inc. representative is responsible for proper configuration of the drive for its primary application, while a
Siemens Building Technologies, Inc. representative is responsible for field panel programming to make use of the drive’s functionality in
the building automation system. As such, there must be coordination between the Yaskawa Electric America and Siemens Building
Technologies representatives to ensure that the programming of the drive is consistent with the particular application requirements. After
verifying that the drive installation and wiring are correct, apply power to the drive. Table 1.1 below lists the parameters and their values
required for proper APOGEE FLN communication and control.
E7 Drive Parameter Settings For APOGEE FLN Communications
Table 1.1 - Drive Communication Parameter Settings
Parameter Number
Digital Operator Display
Settings for APOGEE FLN Communication
b1-01
Reference Source
2: Serial Com
b1-02
Run Source
2: Serial Com
H5-01
Serial Comm Adr
Select the drive address (default = 1Fh (31 dec))
H5-02
Serial Baud Rate
2: 4800 Baud
H5-08
Protocol Select
2: FLN(APOGEE)
CAUTION
A YEA representative should set the drive parameters to their appropriate values. Changes made to
the parameters other than what is listed in the table above can result in damaging the drive or
building equipment.
Programming The E7 Drive For APOGEE FLN
The procedure for programming the E7 drive for communication on an APOGEE FLN network is shown in the table below: Refer to the
E7 User Manual, TM.E7.01, for detailed information on using the E7 Operator.
Table 1.2 - Drive Programming Procedure for APOGEE FLN
Description
Key Operation
Digital Operator Display
Apply Power to the drive
-DRIVE-
Rdy
Frequency Ref
U1-01 =
0.00Hz
- - - - - - - - - - - - - - - - - - - - - - - - - -
U1-02
=
0.00Hz
U1-03
=
0.00A
Select Programming Menu
Press the MENU key until the display matches
the display to the right.
x3
-ADV-
** Main Menu **
- - - - - - - - - - - - - - - - - - - - - - - - - -
Programming
Enter Programming Menu
Press the DATA ENTER key to select the
Programming Menu (A1 blinking)
-ADV-
Initialization
- - - - - - - - - - - - - - - - - - - - - - - - - -
A1-00 = 0
Select Language
Select Sequence Parameters
Press the UP ARROW key until Reference
Source is displayed (b1 blinking).
Note: The item selected will blink.
x2
-ADV-
Sequence
- - - - - - - - - - - - - - - - - - - - - - - - - -
b1-01 = 2
Reference Source