Apogee fln logical analog input summary, Apogee fln logical analog input (lai) summary, Apogee fln point database 4-6 – Yaskawa E7 Apogee FLN User Manual

Page 30

background image

APOGEE FLN Point Database 4-6

APOGEE FLN Logical Analog Input (LAI) Summary

Table 4.2 - APOGEE FLN Application 2721 Logical Analog Input (LAI) Summary (E7 to APOGEE FLN)

Point

Number

Database Descriptor

Units

Slope

Intercept

Default

Min

Max

E7

Parameter

3 FREQ

OUTPUT HZ 0.01 0 0

Fmin

Fmax

U1-02

4 PCT

OUTPUT PCT 0.01 0 0

0

100 –

5 SPEED RPM

1

0

0

Fmin

Fmax

6

CURRENT

AMPS

0.01 or 0.1

0

0

0

DriveMax

U1-03

7 TORQUE PCT

0.1

0

0

0

300

8 POWER KW

0.1

0

0

0

100

U1-08

9 DRIVE

TEMP

DEG

F

1 0

DrvTemp

0

4000

U1-41

10 DRIVE

KWH KWH

0.1 or 1

kVA Dep

0 0

0

32767

U1-29

11 DRIVE

MWH MWH

1 0

0

0

32767

U1-30

12 RUN

TIME HR

1 0

0

0

32767

U1-13

13

DC BUS VOLT

VOLTS

1

0

kVA Dep

0

4000

U1-07

14

AC OUT VOLT

VOLTS

1

0

0

0

kVA Dep

U1-06

15

DRV RATED AMP

AMPS

0.01 or 0.1

0

0

0

kVA Dep

N9-01

16

RUN TIME x 10K

10K HR

1

0

0

0

32767

U1-13

17

FAULT CODE

ERR CD

1

0

0

0

U2-01

62 PID

FEEDBACK HZ 0.01 0 0

0

40

U1-24

66

LST FLT CODE

1

0

0

U2-02

67 FREF.FLT HZ

0.01

0

0

0

400

U2-03

68 OUT

FREQ.FAULT HZ 0.01 0 0 0 400 U2-04

69

OUT CUR.FLT

AMPS

0.1

0

0

0

kVA Dep

U2-05

71

RD PARAM DAT

1

0

75 OUT

VOLT.FLT

VOLTS

0.1 0 0

0

400

U2-07

76 DC

BUS.FLT

VOLTS

1 0

0

0

4000

U2-08

77 OUT

PWR.FLT KW 0.1 0 0

0

400

U2-09

79 PID

DEVIATE PCT

0.01 0

0

0

400

U1-36

87

PID OUT CAP

PCT

0.01

0

0

0

40

U1-37

88 PID

REF PCT

0.01

0

0

0

40

U1-38

89

COMM ERR CD

1

0

0

0

4000

U1-39

99 ERROR

STATUS – 1 0 0

0

255 –