Apogee fln logical analog input summary, Apogee fln logical analog input (lai) summary, Apogee fln point database 4-6 – Yaskawa E7 Apogee FLN User Manual
Page 30

APOGEE FLN Point Database 4-6
APOGEE FLN Logical Analog Input (LAI) Summary
Table 4.2 - APOGEE FLN Application 2721 Logical Analog Input (LAI) Summary (E7 to APOGEE FLN)
Point
Number
Database Descriptor
Units
Slope
Intercept
Default
Min
Max
E7
Parameter
3 FREQ
OUTPUT HZ 0.01 0 0
Fmin
Fmax
U1-02
4 PCT
OUTPUT PCT 0.01 0 0
0
100 –
5 SPEED RPM
1
0
0
Fmin
Fmax
–
6
CURRENT
AMPS
0.01 or 0.1
0
0
0
DriveMax
U1-03
7 TORQUE PCT
0.1
0
0
0
300
–
8 POWER KW
0.1
0
0
0
100
U1-08
9 DRIVE
TEMP
DEG
F
1 0
DrvTemp
0
4000
U1-41
10 DRIVE
KWH KWH
0.1 or 1
kVA Dep
0 0
0
32767
U1-29
11 DRIVE
MWH MWH
1 0
0
0
32767
U1-30
12 RUN
TIME HR
1 0
0
0
32767
U1-13
13
DC BUS VOLT
VOLTS
1
0
kVA Dep
0
4000
U1-07
14
AC OUT VOLT
VOLTS
1
0
0
0
kVA Dep
U1-06
15
DRV RATED AMP
AMPS
0.01 or 0.1
0
0
0
kVA Dep
N9-01
16
RUN TIME x 10K
10K HR
1
0
0
0
32767
U1-13
17
FAULT CODE
ERR CD
1
0
0
0
–
U2-01
62 PID
FEEDBACK HZ 0.01 0 0
0
40
U1-24
66
LST FLT CODE
–
1
0
0
–
–
U2-02
67 FREF.FLT HZ
0.01
0
0
0
400
U2-03
68 OUT
FREQ.FAULT HZ 0.01 0 0 0 400 U2-04
69
OUT CUR.FLT
AMPS
0.1
0
0
0
kVA Dep
U2-05
71
RD PARAM DAT
–
1
0
–
–
–
–
75 OUT
VOLT.FLT
VOLTS
0.1 0 0
0
400
U2-07
76 DC
BUS.FLT
VOLTS
1 0
0
0
4000
U2-08
77 OUT
PWR.FLT KW 0.1 0 0
0
400
U2-09
79 PID
DEVIATE PCT
0.01 0
0
0
400
U1-36
87
PID OUT CAP
PCT
0.01
0
0
0
40
U1-37
88 PID
REF PCT
0.01
0
0
0
40
U1-38
89
COMM ERR CD
–
1
0
0
0
4000
U1-39
99 ERROR
STATUS – 1 0 0
0
255 –