APOGEE FLN Point Database 4-5

Table 4 .1 - APOGEE FLN Application 2721 Point Number Summary

Point

Number

Point

Type

Point Name

Factory Default

(SI Units)

Engr. Units

(SI Units)

Slope

(SI Units)

Intercept

(SI Units)

On

Text

Off

Text

E7

Parameter

92 LAO CBL

LOSS

TMR

2

SEC

0.1

0

H5-09

{93}

LDI

OK.FAULT

OK

1

0

FAULT

OK

U1-12 (Bit 7)

{94}

LDO

RESET

FAULT NO

– 1 0

RESET

NO –

{95}

LDI

DRV COMM ERR

NO FLT

1

0

FAULT

NO FLT

{96} LDO EXTERNAL

FLT

OK

1

0

FAULT OK

{97}

LDI

MF IN 5 MON

OFF

1

0

ON

OFF

U1-10 (Bit 6)

{99} LAI ERROR

STATUS

0

1

0


This manual is related to the following products: