beautypg.com

Apogee fln point list summary, Apogee fln point database 4-3 – Yaskawa E7 Apogee FLN User Manual

Page 27

background image

APOGEE FLN Point Database 4-3

APOGEE FLN Point List Summary

This database is for APOGEE FLN Application 2721 and features 97 logical points: 29 Logical Analog Inputs (LAI), 35 Logical Analog
Outputs (LAO), 19 Logical Digital Inputs (LDI) and 14 Logical Digital Outputs (LDO). These points configure, control or monitor the
operation of the Drive.

Information to consider when referencing this table:

1. Points not listed are not used in this application.
2. A single value in a column means that the value is the same in English units and in SI units.
3. Point numbers that appear in brackets, e.g. {03}, can be unbundled at the field panel.

Table 4 .1 - APOGEE FLN Application 2721 Point Number Summary

Point

Number

Point

Type

Point Name

Factory Default

(SI Units)

Engr. Units

(SI Units)

Slope

(SI Units)

Intercept

(SI Units)

On

Text

Off

Text

E7

Parameter

01 LAO

CTLR

ADDRESS

31

1

0

H5-01

02 LAO APPLICATION

1

0

{03} LAI FREQ

OUTPUT

0

HZ

0.01

0

U1-02

{04} LAI PCT

OUTPUT

0

PCT

0.01

0

{05} LAI

SPEED

0

RPM

0.01

0

{06} LAI CURRENT

0

AMPS

(A) 0.01

0

U1-03

{07} LAI

TORQUE

0

PCT

0.1

0

{08} LAI

POWER

0

KW

0.1

0

U1-08

{09}

LAI

DRIVE TEMP

0

DEG F / C

1

0

U1-41

{10} LAI DRIVE

KWH

0

KWH

0.1

0

U1-29

{11} LAI

MWH

0

MWH

1

0

U1-30

{12} LAI RUN

TIME

0

HRS

1

0

U1-13

{13} LAI DC

BUS

VOLT

0

PCT

1

0

U1-07

{14}

LAI

AC OUT VOLT

0

VOLTS (V)

0.1

0

U1-06

15 LAI PAR

N9.01

0

AMPS

(A) 0.01

0

N9-01

{16} LAI RUN

TIMEX10K

0

10K

HR

1

0

U1-13

{17} LAI FAULT

CODE

0

1

0

U2-01

{18}

LDI

MINOR FLT

NO FLT

1

0

FAULT

NO FLT

U1-12 (Bit 6)

{19}

LDI

MAJOR FLT

NO FLT

1

0

FAULT

NO FLT

U1-12 (Bit 7)

20 LAO OVRD

TIME

1

HRS

1

0

{21}

LDI

FWD.REV

FWD

1

0

REV

FWD

U1-12 (Bit 2)

{22} LDO CMD

REV.STOP

STOP

1

0

REV STOP

{23}

LDI

RUN.STOP

STOP

1

0

RUN

STOP

U1-12 (Bit 0)

{24} LDO CMD

RUN.STOP

STOP

1

0

FWD STOP

{25}

LDI

ZERO SPEED

OFF

1

0

ON

OFF

U1-12 (Bit 1)

{26}

LDI

SPEED AGREE

NO AGR

1

0

AGREE

NO AGR

U1-12 (Bit 4)

{27}

LDI

DRIVE READY

NOTRDY

1

0

READY

NOTRDY

U1-12 (Bit 5)

{28} LDI LOC.REM

MON REMOTE

1

0

LOCAL

REMOTE

{29} LDO

DAY.NGT

DAY

1

0

NGT DAY

30

LAO

CURRENT LIM

0

AMPS (A)

0.01

0

E2-01

31 LAO ACCEL

TIME

1

0

SEC

0.1

0

C1-01

32 LAO DECEL

TIME

1

0

SEC

0.1

0

C1-02

33 LDO LOCK

PANEL

UNLOCK

1

0

LOCK

UNLOCK –

35 LDO RUN

ENABLE

STOP

1

0 ENABLE

STOP

36 LAO STALL

PRE

RN

90

PCT

30

0

L3-06

37 LAO STALL

PRE

AC

120

PCT

1

0

L3-02

38

LAO

FREQ UP LIM

100

PCT

0.1

0

D2-01

39 LAO

FREQ

LOW

LIM

0

PCT

0.1

0

D2-02

{40}

LDI

MULTI OUT 1

OFF

1

0

ON

OFF

U1-11 (Bit 0)

{41}

LDI

MULTI OUT 2

OFF

1

0

ON

OFF

U1-11 (Bit 1)

This manual is related to the following products: