Device object – Yaskawa BACnet MS/TP SI-B3/V User Manual
Page 42

Object ID
Object Name
Modbus
Address
Active Text
Inactive
Text
PV Access
BV40
Low Voltage Detect
002CH:bit 7
ON
OFF
R
BV41
Base Block
002CH:bit 8
ON
OFF
R
BV42
Frequency Ref Mode
002CH:bit 9
COM
LOCAL
R
BV43
Run Command Mode
002CH:bit 10
COM
LOCAL
R
BV44
Overtorque Detect
002CH:bit 11
ON
OFF
R
BV45
Frequency Refer Lost
002CH:bit 12
ON
OFF
R
BV46
Retry Error
002CH:bit 13
ON
OFF
R
BV47
Modbus Comms Error
002CH:bit 14
ON
OFF
R
BV48
Modbus Timeout Error
002CH:bit 15
ON
OFF
R
BV49
CRC Error
003DH:bit 0
ON
OFF
R
BV50
Invalid Data Length
003DH:bit 1
ON
OFF
R
BV51
Parity Error
003DH:bit 3
ON
OFF
R
BV52
Overrun Error
003DH:bit 4
ON
OFF
R
BV53
Framing Error
003DH:bit 5
ON
OFF
R
BV54
Timeout Error
003DH:bit 6
ON
OFF
R
BV55
<1>
Parameter Accept
0910H:bit 0
ON
OFF
W
BV56
<1>
Parameter Enter
0900H:bit 0
ON
OFF
W
BV57
Drive Comms Error
-
ON
OFF
R
<1>
Refer to Accessing Drive Parameters and the Enter Command on page 43
for an explanation of how to read
and write drive parameters not listed in the analog or binary objects.
u
Device Object
The Device Object fully describes the BACnet device to the network. Notable is that the
Device Object Instance ID and the Device Object Name are configurable.
The Device Object Instance ID is a unique internetwork-wide numerical value. It is a 22-bit
value that can range from 0 to 4,194,303. It is configurable by parameters F6-48 and F6-49.
Any changes to these parameters will not take effect until the power is cycled to the drive.
The Device Object Name is a unique internetwork-wide character string. It is a 20-character
string. It is writable from the BACnet network. Any new string written will not take effect
until the power is cycled to the drive.
9 BACnet Objects Supported
42
YASKAWA TOEP YAICOM 19A V1000 Option BACnet MS/TP SI-B3/V Installation & Technical Manual