4 option components – Yaskawa BACnet MS/TP SI-B3/V User Manual
Page 13

The operational states of the option LEDs after completion of the BACnet power-up diagnostic
. Wait at least 2 seconds for the power-up diagnostic
process to complete before verifying LED states.
Table 3 Option LED States
Name
Display
Operating Status
Remarks
Color
Status
MS
–
OFF
Power supply OFF
Power is not being supplied to the drive.
Green
ON
Normal operation
The option is operating normally and
initialization is complete.
Green
Flashing
Standby/Initializing
The option is in process of configuring or
waiting for configuration information.
Red
Flashing
Minor fault
The option has detected a recoverable
minor fault such as incomplete
configuration.
Red
ON
Major fault
The option has detected an unrecoverable
major fault.
Green/Red
Flashing
Option self-test
The option is in self-test mode.
NS
–
OFF
Power supply OFF
–
Green
ON
Connected
The device is currently communicating on
the network.
Green
Flashing
Not connected
The device currently is not communicating,
but is correctly configured. The state is
“waiting” for communication to resume.
Red
Flashing
Minor fault
A minor recoverable fault has occurred.
Red
ON
Major fault
A non-recoverable major network fault has
occurred.
Green/Red
Flashing
Network test
Power-up sequence and testing
TX
–
OFF
No data being sent to the
network
This node is not sending any data.
Green
Flashing
Data being sent to the
network
This node is sending network data.
RX
–
OFF
No data seen on the
network
The option is not physically connected to
the network or there is no network activity.
Green
Flashing
Data is seen on the
network
The option is connected to a network.
4 Option Components
YASKAWA TOEP YAICOM 19A V1000 Option BACnet MS/TP SI-B3/V Installation & Technical Manual