u
BACnet Node Addressing
The BACnet node address is configurable by parameter F6-45 in the drive. This defines the
physical address of the drive on the MS/TP network. In addition, both the Device Object
Instance Identifier (parameters F6-48 and F6-49) and the Device Object Name are
configurable. These allow the drive to have a virtual address and simplify the controller
configuration.
After setting the addressing, a controller can initiate communication to the drive. The drive
will perform the specified function and then send a response back to the controller. The drive
will usually respond immediately, but may delay its response until it gets the token for
commands that may take extra local processing time.
u
Electronic Protocol Implementation Conformance Statement
(EPIC) Files
For easy network implementation of drives equipped with the SI-B3/V option, an EPIC file
can be obtained from:
U.S.: http://www.yaskawa.com
Other areas: Contact a Yaskawa representative.
Refer to BACnet Protocol Implementation Conformance Statement (PICS) on page 45
for the SI-B3/V PICS.
5 Installation Procedure
28
YASKAWA TOEP YAICOM 19A V1000 Option BACnet MS/TP SI-B3/V Installation & Technical Manual