6 related drive parameters – Yaskawa BACnet MS/TP SI-B3/V User Manual
Page 30

No.
(Addr.
Hex)
Name
Description
Values
F6-08
(036A)
<3>
Reset
Communication
Parameters
0: Communication-related parameters (F6-oo/F7-oo) are
not reset when the drive is initialized using A1-03.
1: Reset all communication-related parameters
(F6-oo/F7-oo) when the drive is initialized using A1-03.
Default: 0
Range: 0, 1
F6-14
(03BB) bUS Error Auto Reset
0: Disabled
1: Enabled
Default: 0
Range: 0, 1
F6-45
(02FB) Drive Node Address
Sets the BACnet MS/TP MAC address (physical node
address).
Default: 1
Range: 0 to 127
F6-46
(02FC)
Communication
Speed Selection
Sets the communication speed.
0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19200 bps
5: 38400 bps
6: 57600 bps
7: 76800 bps
8: 115200 bps
Default: 3
Range: 0 to 8
F6-47
(02FD)
Drive Transmit Wait
Time
Sets the time the drive waits after receiving data from a master
before transmitting response data.
Default: 5 ms
Range: 5 to 65
F6-48
(02FE)
<2>
BACnet Device
Object Identifier 0
Set the Instance Identifier of the BACnet Device Object,
where the F6-48 value is the least significant word.
Default: 1
Range: 0 to FFFFH
F6-49
(02FF)
<2>
BACnet Device
Object Identifier 1
Set the Instance Identifier of the BACnet Device Object,
where the F6-49 value is the most significant word.
Default: 0
Range: 0 to 3FH
F7-16
(03F4)
Communication Loss
Timeout
Sets the timeout value for communication loss detection in
tenths of a second.
Example: An entered value of 100 represents 10.0 seconds.
Default: 0.0
Min.: 0.0
Max.: 30.0
<1>
To start and stop the drive with the option master device using serial communications, set b1-02 to 3. To control
the drive frequency reference via the master device, set b1-01 to 3.
<2>
These parameters set the Instance Identifier of the BACnet Device Object, where the F6-48 value is the least
significant word and the F6-49 value is the most significant word.
Example 1: Set the Device Object Instance Identifier of "1234". 1234 decimal is equal to 4D2H (hexadecimal).
Set F6-48 to 4D2H and F6-49 to 0.
Example 2: Set Device Object Instance Identifier to "1234567". 1234567 decimal is equal to 12D687H. Set
F6-48 to D687H and set F6-49 to 12H.
<3>
Parameter setting value is not reset to the default value when the drive is initialized.
6 Related Drive Parameters
30
YASKAWA TOEP YAICOM 19A V1000 Option BACnet MS/TP SI-B3/V Installation & Technical Manual