VS-656DC5 User’s Manual
5 - 20
Pr
ot
ec
ti
o
n
Fu
nc
ti
on
s
Instantaneous Overcurrent
Stops at approximately 200% converter input current
Fusing
Stops upon open fusing
Overload
Stops at 1-minute at 150% rated current (power and regenerative)
Undervoltage (output)
Stops at approx. DC380V or less
Stops at approx. DC570V or less
Undervoltage (input)
Stops at approx. AC300V or less
Stops at approx. AC460V or less
Overvoltage
Stops at approx. DC820V or less
Stops at approx. DC1140V or less
Cooling fin Overheat
Protected by thermistor
Power Phase Loss
Stops at power phase loss detection
Ground Fault Detection
Stops at a ground fault current approx. 50% of converter input current
Supply Frequency Error
Stops at a fluctuation of ±3Hz or more from rated input frequency
Charge Display
Displayed until the main output voltage is under approx. 50V
Momentary Power Loss
Operation can continue according to the parameter settings for 2sec. or
less at momentary power loss
En
v
iro
n
m
en
tal
Specification
s
Usage Location
Indoors (no gas, grime, or dust)
Ambient Temperature
-10C~+45C
Humidity
90%RH or less (no condensation)
Vibration
1G at under 20Hz, up to 0.2G is allowable at 20~50Hz
Voltage Class
400V Class
600V Class
Model CIMR-D5A
4200
4400
4600
4800
6300
6600
6900
6000