Alarm display details – Yaskawa Varispeed-656 DC5 Converter User Manual

Page 22

background image

VS-656DC5 User’s Manual

20 - 20

Alarm Display Details

Alarms do not operate the error contact outputs, and will automatically return to the original
run state when their cause has been removed. Alarms flash when displayed.

Alarm

Display

Alarm Display

Content

Description

Countermeasures

UV

Undervoltage
Detected

The main DC voltage was less than L2-05
(undervoltage detection level) while stopped
or during momentary power loss.

OV

OV While
Stopped

The main circuit DC voltage has exceeded the
OV level.

Excessive regen load

OL

Converter
Input Overload

Input load capacity level has been exceeded.

Reduce load

OH

Cooling Fin
Overheat

Cooling fin temperature has exceeded L8-02

• Check fin, ambient temper-

ature

• Check filter, fin

EF3

Control Circuit
Terminal 3
External Error

An external error (minor fault selection) was
input from control circuit terminal 3.

Check input terminal.

EF4

Control Circuit
Terminal 4
External Error

An external error (minor fault selection) was
input from control circuit terminal 4.

EF5

Control Circuit
Terminal 5
External Error

An external error (minor fault selection) was
input from control circuit terminal 5.

EF6

Control Circuit
Terminal 6
External Error

An external error (minor fault selection) was
input from control circuit terminal 6.

EF7

Control Circuit
Terminal 7
External Error

An external error (minor fault selection) was
input from control circuit terminal 7.

EF8

Control Circuit
Terminal 8
External Error

An external error (minor fault selection) was
input from control circuit terminal 8.