Error displays and countermeasures (continued) – Yaskawa Varispeed-656 DC5 Converter User Manual
Page 19

VS-656DC5 User’s Manual
17 - 20
UV1
Main Circuit
Undervoltage
While running, the main circuit voltage fell
beneath the PUV detection level and
exceeded the momentary power loss ride-
through time.
Detection level
400V Class: Approx. 380V DC or less
600V Class: Approx. 570V DC or less
• Check the wiring on power
side devices
• Fix the source voltage
UV2
Control Circuit
Undervoltage
An undervoltage has occurred in the control
circuit
UV3
MC Answer
Fault
The in rush current suppressing contactor
opened during operation.
AUv
Supply Under-
voltage
While running, an undervoltage occurred on
the power supply side.
Detection level
400V Class: Approx 300V AC or less
600V: Approx. 400V AC or less
FdEv
Power Fre-
quency Error
The power frequency has exceeded the toler-
ance (F1-10)
SrC
Input Phasing
Error
The phase cycle direction on the input side
changed after control power input.
OC
Overcurrent
The Converter input current exceeded the OC
level.
• Output short
• Decrease power
OV
Overvoltage
The main circuit DC voltage exceeded the
OV level
Detection level
400V Class: Approx 800V DC or higher
600V: Approx 1040V DC or higher
Excessive regen load
OH
Cooling Fin
Overheat
The cooling fin temperature has exceeded the
value in L8-02.
• Check fin, ambient temper-
ature
• Check the filter, fin
OH1
Cooling Fin
Overheat
The cooling fin temperature has exceeded the
tolerance.
OL
Converter Input
Overload
The input overload level has been exceeded.
Decrease load
Error Displays and Countermeasures (Continued)
Error
Display
Error Display
Content
Description
Countermeasures