UV1

Main Circuit
Undervoltage

While running, the main circuit voltage fell
beneath the PUV detection level and
exceeded the momentary power loss ride-
through time.
Detection level
400V Class: Approx. 380V DC or less
600V Class: Approx. 570V DC or less

• Check the wiring on power

side devices

• Fix the source voltage

UV2

Control Circuit
Undervoltage

An undervoltage has occurred in the control
circuit

UV3

MC Answer
Fault

The in rush current suppressing contactor
opened during operation.

AUv

Supply Under-
voltage

While running, an undervoltage occurred on
the power supply side.
Detection level
400V Class: Approx 300V AC or less
600V: Approx. 400V AC or less

FdEv

Power Fre-
quency Error

The power frequency has exceeded the toler-
ance (F1-10)

SrC

Input Phasing
Error

The phase cycle direction on the input side
changed after control power input.

OC

Overcurrent

The Converter input current exceeded the OC
level.

• Output short
• Decrease power

OV

Overvoltage

The main circuit DC voltage exceeded the
OV level
Detection level
400V Class: Approx 800V DC or higher
600V: Approx 1040V DC or higher

Excessive regen load

OH

Cooling Fin
Overheat

The cooling fin temperature has exceeded the
value in L8-02.

• Check fin, ambient temper-

ature

• Check the filter, fin

OH1

Cooling Fin
Overheat

The cooling fin temperature has exceeded the
tolerance.

OL

Converter Input
Overload

The input overload level has been exceeded.

Decrease load

Error Displays and Countermeasures (Continued)

Error

Display

Error Display

Content

Description

Countermeasures