Cpf error details – Yaskawa Varispeed-656 DC5 Converter User Manual
Page 21

VS-656DC5 User’s Manual
19 - 20
CPF Error Details
Error
Display
Error Display
Content
Description
Countermeasures
CPF00
Control Circuit
Error 1 (Opera-
tor Transmis-
sion Error)
• Communication between the controller
and operator not established even though 5
sec. have passed since power ON.
• MPU peripheral element check error
• Re-connect operator and
connector
• Check wiring on control cir-
cuit power source
• Replace controller card
CPF01
Control Circuit
Error 2 (Opera-
tor Transmis-
sion Error)
• After communication has been established
between the controller and the operator
after power ON, a 2 sec. + transmission
error occurred.
• MPU peripheral element check error
• Re-connect operator and
connector
• Check wiring on control cir-
cuit power source
• Replace controller card
CPF02
Base Block
Circuit Fault
Converter Controller Fault
Replace control card
CPF03
EEPROM Fault
CPF04
CPU-Internal
A/D Converter
Fault
CPF05
CPU-External
A/D Converter
Fault
CPF06
Option Con-
nection Error
Option card improperly connected.
Re-insert option card.
CPF07
PWM Timer
Error
Converter Controller Fault
Replace control card
CPF08
DPRAM BCC
Check Error
CPF09
DPRAM Inter-
connection
Diagnostic
Error
CPF10
DPRAM Write
Error
CPF22
Option Device
Code Error
Incompatible option is connected.
Check the connected options.
CPF24
Converter
Card Error
Converter card A/D conversion error.
Replace converter card.