Parameter lists, Dc5 parameter list – Yaskawa Varispeed-656 DC5 Converter User Manual
Page 15

VS-656DC5 User’s Manual
13 - 20
7. Parameter Lists
DC5 Parameter List
Parameter
No.
Name
Initial
Value
Setting Range
Change
on the
Fly?
Access
Level
Notes
A1-01
Access Level
2
0~9999
Y
Q
0: Monitor-dedicated
2: Quick-Start (Q)
3; Basic (B)
4: Advanced (A)
A1-02
Initialization
0000
0000~9999
N
Q
2220: Parameter initialization
A1-03
Password 1 (For Input)
0
0000~9999
N
Q
B1-01
Voltage Reference Selection
0
0
N
Q
0: Digital Operator
B1-02
Run Command Selection
1
0/1
N
Q
0: Digital Operator
1: Control Circuit Terminal
B1-06
Sequence Input Double Read
Selection
1
0/1
N
A
0: 1msec double read
1: 5msec double read
C1-01
Accel Time
10.0
0.0~6000.0sec
Y
Q
C1-02
Decel Time
10.0
0.0~6000.0sec
Y
Q
C5-01
AVR Proportional (P) Gain
10.00
1.00~300.00
Y
B
C5-02
AVR Integral (I) Time
0.500
0.000~10.000sec
Y
B
C5-06
AVR Primary Delay Time
0.000
0.000~0.500sec
N
B
D1-01
Voltage Reference
See Notes
600V~680V (400V-class)
750V~900V (600V-class)
Y
Q
660 (400V-class)
860 (600V-class)
F1-10
Input Frequency Deviation
Detection Level
3.0
0.0~10.0Hz
N
A
F1-11
Input Frequency Deviation
Detection Delay Time
70
0~255msec
N
A
H1-01
9CN-19 Terminal Selection
(Multi-function input)
0F
00~FF
N
0F: Unused
H1-02
9CN-20 Terminal Selection
(Multi-function input)
0F
00~FF
N
0F: Unused
H1-03
9CN-21 Terminal Selection
(Multi-function input)
0F
00~FF
N
0F: Unused
H1-04
9CN-22 Terminal Selection
(Multi-function input)
0F
00~FF
N
0F: Unused
H1-05
9CN-23 Terminal Selection
(Multi-function input)
0F
00~FF
N
0F: Unused
H1-06
9CN-24 Terminal Selection
(Multi-function input)
0F
00~FF
N
0F: Unused
H2-01
TB2-4, 5 Terminal Selection
(Multi-function input)
0F
00~FF
N
0F: Unused
H2-02
10CN-10 Terminal Selection
(Multi-function input)
0F
00~FF
N
0F: Unused
H2-03
10CN-12 Terminal Selection
(Multi-function input)
0F
00~FF
N
0F: Unused
H2-03
10CN-14 Terminal Selection
(Multi-function input)
0F
00~FF
N
0F: Unused
H2-03
10CN-16 Terminal Selection
(Multi-function input)
0F
00~FF
N
0F: Unused
H2-03
TB2-1, 2, 3 Terminal Selection
(Multi-function input)
0E
00~FF
N
0E: Error
L1-02
Output OL (OL2) Operation
Time
60.0
1.0~120.0sec
N
B