beautypg.com

Yaskawa MP3200iec User Manual

Page 37

background image

15 MECHATROLINK-III Synchronization between Modules

YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5

35

15

MECHATROLINK-III Synchronization between Modules

‹

Communications Cycle and the Number of Slave Stations

The relationship between the MECHATROLINK communications cycle and the number of slave stations is given in the
following tables.

„

Cascaded Connections

„

Star Connections

„

Mixed Cascaded/Star Connections

Note: The above connection conditions assume that the following conditions are met: Number of transmission bytes: 48, Distance

between stations: 100 m., Number of retries: 1.

NOTICE: If the SigmaWin+ is connected through a Machine Controller, the SigmaWin+ may not be usable if there are too many
SERVOPACK stations connected. If this occurs, either connect the SigmaWin+ to the SERVOPACK (CN7) directly, or increase the
communications cycle.

Communications

Cycle

Number of Connected

Stations

Connection Conditions

125

μs

1 to 3

250

μs

1 to 7

500

μs

1 to 12

1 ms

1 to 21

1.5 ms

1 to 27

2 ms

1 to 32

3 ms

1 to 38

If more than 32 stations are connected, two ports must be used.
No more than 32 stations can be connected to a single port.

4 ms

1 to 62

If no more than 32 stations are connected, two ports must be used.
No more than 32 stations can be connected to a single port.

Communications Cycle

Number of Connected Stations

125

μs

1 to 4

250

μs

1 to 8

500

μs

1 to 14

1 ms

1 to 32

1.5 ms

1 to 62

2 ms

1 to 62

3 ms

1 to 62

4 ms

1 to 62

Communications Cycle

Number of

Connected Stations

Connection Conditions

125

μs

1 to 4

Only star connections can be used.

250

μs

1 to 8

A single cascaded connection series must consist of no more than 2 stations.

500

μs

1 to 14

A single cascaded connection series must consist of no more than 6 stations.

1 ms

1 to 29

A single cascaded connection series must consist of no more than 7 stations.

1.5 ms

1 to 42

A single cascaded connection series must consist of no more than 8 stations.

2 ms

1 to 42

A single cascaded connection series must consist of no more than 16 stations.

3 ms

1 to 42

A single cascaded connection series must consist of no more than 18 stations.

4 ms

1 to 62

A single cascaded connection series must consist of no more than 21 stations.