12 Self-Configuration
12
Self-Configuration
DIP Switch
Self-Configuration after Adding Devices such as Servopacks
By performing the following operation, a definition for devices detected on the MECHATROLINK-III network is
created. Before performing the operation, turn ON the power supply for each network node.
MotionWorks IEC
The MotionWorks IEC (Express or Pro) configuration can detect the configuration and provide the user with
configuration choices. If a StartUp Configuration was already saved on the controller, the self-configure function will not
allow new devices to be discovered. In this case, add them offline manually first.
STOP
SUP
INIT
CNFG
MON
TEST
1. Turn OFF the power supply
Turn OFF the 24 VDC power supply of the MP3200Siec.
2. Set DIP Switches
Turn ON CNFG in the DIP switch (SW1) of the MP3200Siec.
ࠉࠉࠉ
3. Turn ON the power supply
Turn ON the 24 VDC power supply of the MP3200Siec.
4. Check the LED Indicators
Check that LED display of the MP3200Siec basic module is
changed as follows:
ۻ
ۻ
5. DIP switch resetting
Turn the CNFG DIP switch (SW1) of the MP3200Siec to OFF.