11 EMC Installation Conditions

35

11 EMC Installation Conditions

This section describes the recommended installation conditions that

satisfy EMC guidelines for each model of the SGDV SERVOPACK. The

conditions required for the standard type (base-mounted) of the

SERVOPACK are described. Refer to this section for other

SERVOPACK models such as the rack-mounted types as well.

This section describes the EMC installation conditions satisfied in test

conditions prepared by Yaskawa. The actual EMC level may differ

depending on the actual system’s configuration, wiring, and other

conditions. However, because this product is built-in, check that the

following conditions are still met after being installed in the user’s

product.

The applicable standards are EN55011/A2 group 1 class A, EN61800-3,

and EN61000-6-2.

Ethernet Communication Cables: Use a category 5 or higher cable with

double, aluminum tape and braided shielding according to the standard

EN50288-2-2.