Control Board Inputs/Outputs

Step 12 (for GPD 506/P5 models)

Analog Output

6. Turn potentiometer RV1 until the frequency reference is 60Hz and close switch #1. The bar

graph DSP1 will be fully illuminated when the output reaches 60Hz. Open switch #1.

Digital Output

7. Monitor LED #1 (terminal M1), the LED should be off. Command the inverter to

run at 60Hz, the LED should go on. Stop the inverter by opening switch #1.

Fault Contacts

8. When the inverter is not in a fault state, LED #3 (terminal MB) will be on. Close switch #3,

EF3 will be displayed and LED #2 (terminal MA) will illuminate. Open switch #3 and
press the reset key.

9. Perform a 2-wire factory initialization by setting n001 =8.

10. Remove power and remove the test board.