beautypg.com

Control board inputs/outputs – Yaskawa GPD 506/P5 Section Two User Manual

Page 23

background image

PP.P5G5.02Troubleshoot

Page 23

Rev. 06/11/2003

Control Board Inputs/Outputs

Step 12 (for GPD 515/G5 models)

The following procedure may be used to thoroughly test the functions of the contact
inputs/outputs and analog inputs/outputs of the control board.
(A GPD515/G5 test board is required to perform these steps)

1. With the power removed, install the test board to the terminal strip of the control board.

2. Apply power and perform a 2-wire factory initialization by setting A1-03 =2220. Change the

access level (A1-01) to the advanced level (set value 4)

Digital & Analog Input Terminals

3. View monitor U1-10 (Input Term Sts), close and then open switches 1 through 8 and

watch the display change from a “0” to a “1”.

4. View monitor U1-01 (Frequency Ref) and turn potentiometer RV1 (terminal 13) and

watch the reference change.

5. Close switch #5, view monitor U1-01 (Frequency Ref) and turn potentiometer

RV2 (terminal 16) and watch the reference change. Open switch #5.

Analog Outputs

6. Change parameter H4-04 (terminal 23 sel) to 1 (frequency ref) and H4-05 (terminal 23 gain)

to 1, turn potentiometer RV1 until the frequency reference is 60Hz. The bar graph DSP2
should be illuminated. Close switch #1 and the bar graph DSP1 should fully illuminate
when the output reaches 60 Hz. Open switch #1.