Run The Motor
Step 10
1. Making sure that the power is not applied to the inverter, and the DC Bus
voltage is below 10V, hook up the motor to the output terminals labeled
T1, T2, and T3.
2. Apply power to the inverter.
3. Set the acceleration time and the deceleration time to 10 seconds.
GPD 515/G5
GPD 506/P5
Acceleration time (C1-01) Acceleration time 1 (n019)
Deceleration time (C1-02) Deceleration time 1 (n020)
4. Set the frequency reference for 6 Hz.
5. Give the inverter a forward run command. Observe the motor for abnormal
operation. Repeat this step giving the inverter a reverse run command.
6. Set the frequency reference to 30 Hz and run the motor in both directions
once again observing the operation.
7. Set the frequency reference to 60 Hz and run the motor once again.
8. Give the inverter a stop command.