Symbol import procedure, Function block startup procedure – Yaskawa MP2300 User Manual
Page 9

MP2300 Quick Reference Guide Rev1.5
Function Block Startup Procedure
First complete the MP2300 Startup Procedure
There should be a new controller folder
Step Instruction
Detail
1
Acquire project file
FB040823.MAL or equivalent. Download to C:\ or any directory without
spaces.
3
Extract MAL file to
controller files on
hard drive*
R-click Controller folder, Transfer, Selected Files, From Another Drive to
MPE720. Find *.MAL file. *Check the FUNC box. Then click "transfer"
button. Takes about 30 seconds. Close window when complete.
4
Transfer Function blocks
to Controller*
R-Click controller folder, Transfer, Selected Files, From MPE720 to
Controller. *Check the FUNC box. Then click "transfer" button. Transfer
takes almost 4 minutes with serial connection. Close window when complete.
5
Save to Flash
Click the Black Diskette Icon. When the window pops up, click the leftmost
button (Compar/save) and accept other defaults. Close window when
complete.
6
Save to Hard Disk
R-Click controller, Transfer - All files - From Controller to MPE720. Uncheck
registers or it will take over 7 minutes.*
7
Cycle Power
Cycle power is needed for initialization drawings (A drawings) to run
*
To start a totally blank Function Block project, only check FUNC box and all detail. To start with the pre-
made Function Block template, check both DWG and FUNC and under each detail select "all".
Log ON (online)
2
R-Click Controller folder, Log OFF. R-Click controller folder, check "online".
Double-click Controller folder to log on. The default User Name and
Password are both USER-A
Page 9 of 14