Ethernet/ip option kit cm092 – Yaskawa CM092 User Manual
Page 6

Yaskawa America, Inc. –
IG.AFD.26, Page 6 of 16
Date: 08/18/2011 Rev: 11-08
EtherNet/IP Option Kit
CM092
17. Drive labeling and EDS files
18. EtherNet/IP Option Card fault codes
a. Place the supplied MAC ID label on the side of the drive either above or below the drive nameplate.
Nameplate for all drives except G5HHP drives Nameplate for G5HHP drives
b. To simplify the drive configuration, EDS file can be ob
Comms-Ethernet. Then select the appropriate EDS file based on the drive series and the latest version from those listed. EDS files for individual drive
models are compressed into a single Zip file.
MODEL:
CIMR-G7U20P4
SPEC: 20P41A
INPUT: AC3PH 200 - 240V 50/60Hz 3.8A
OUTPUT: AC3PH 0 - 240V 0 – 400Hz 3.2A 1.2kVA
O/N:
MASS: 3.0kg
S/N:
1W0149999991W0001
PRG:
1W0149999991W0001
FILE NO: E131457
MAC ID: 00-20-B5-24-11-13
INVERTER MODULE
CODE NO.: EUJ615162
SERV. NO.: 4W06X7847760001
MASS:
125KG
YASKAWA AMERICA, INC.
MAC ID: 00-20-B5-24-11-13
The table of EtherNet/IP Option Card fault codes returned by the drive is shown below. Refer to the appropriate drive user and/or programming manual(s) for drive
specific information on the fault returned.
Note: G5HHP drive differences are denoted by bold text inside carets <> in the following table.
EtherNet/IP Fault Code
[hex]
Description
EtherNet/IP
Fault Code
[hex]
Description
0000h
None
5300h
OPE errors (01,02,03,05,06,07,08,09,10,11)
2120h
Ground Fault (GF)
6320h
EEPROM R/W Error (ERR)
2130h
Short Circuit (SC)
7110h
Dynamic Braking Transistor (RR)
2200h
Inverter Overload (OL2)
7112h
Dynamic Braking Resistor (RH)
2220h
Motor Overload (OL1)
7301h
PG Open (PGO)
2221h
Overtorque Detection 1 (OL3)
7310h
Overspeed Detection (OS)
2222h
Overtorque Detection 2 (OL4)
7310h
Speed Deviation (DEV)
2300h
Overcurrent (OC)
7500h
EtherNet/IP Communication Error (BUS)
2310h
High Slip Braking (OL7)
8110h
Feedback Loss (FBL)
3130h
Input Phase Loss (PF)
8313h
Zero Servo Fault (SVE)
3130h
Output Phase Loss (LF)
8321h
Out of Control (CF)
3210h
DC Bus Overvoltage (OV)
8321h
Undertorque Detection 1 (UL3)
3220h
DC Bus Undervoltage (UV1)
8321h
Undertorque Detection 2 (UL4)
3222h
MC Answerback (UV3)
9000h
External Fault on Terminal S3 (EF3)
4200h
Heatsink Over-temperature (OH)
9000h
External Fault on Terminal S4 (EF4)
4210h
Heatsink Maximum Temperature
(OH1)
9000h
External Fault on Terminal S5 (EF5)
4300h
Motor Overheat 1 (OH3)
9000h
External Fault on Terminal S6 (EF6)
4310h
Motor Overheat 2 (OH4)
9000h
External Fault on Terminal S7 (EF7)
5110h
CTL PS Undervoltage (UV2)
9000h
External Fault on Terminal S8 (EF8)
5120h
DC Bus Fuse Open (PUF)
9000h
External Fault Through Option Card (EF0)
5300h
Operator Disconnected (OPR)
-
-