Installing Support Brackets (Figure 49)

A horizontal pipe support MUST BE used for each 3 feet of horizontal

run. The pipe supports should be placed around the pipe and nailed

in place to framing members. There MUST BE a 3 inch clearance

to combustibles above flue pipe and elbows and 1 inch clearance

on both sides and bottom of the flue pipe to combustibles on all

horizontal pipe sections and elbows.
Vertical runs of this vent systems must be supported every 4 feet

above the appliance flue outlet by wall brackets attached to the

vent pipe and secured with nails or screws to structural framing

members.

Figure 49

Installing Firestops (Figures 50, 51, 52, and 53)

Firestops are required for safety whenever the vent system passes

through an interior wall, an exterior wall, or a ceiling. These firestops

act as a firebreak heat shield and as a means to insure that minimum

clearances are maintained to the vent system.
Horizontal runs in the vent system which pass through either interior

or exterior walls, require the use of wall firestops on both sides of

the wall through which the vent passes.
Cut an appropriate sized hole in wall. See Figure 50. Position

firestop on interior side of wall for hole.
Attention: Wall firestop hole is off-set towards bottom of wall

opening. Secure with nails or screws. Continue the vent run through

the firestop. See Figure 50.

Figure 50

Vertical runs of this system which pass through ceilings require the

use of ONE (1) ceiling firestop at the hole in each ceiling through

which the vent passes.
Position a plumb bob directly over the center of the vertical vent

component and mark the ceiling to establish the center point of the

vent. Drill a hole or drive a nail through this center point and check

the floor above for any obstructions such as wiring or plumbing

runs. Reposition the appliance and vent system, if necessary, to

accommodate ceiling joists and/or obstructions.
Cut an appropriate sized hole through the ceiling, using the center

point previously marked. See Figure 51. Frame the hole with

framing lumber the same size as the ceiling joists. See Figure 51.

If the area above the ceiling is NOT an attic, position and secure

the ceiling firestop on the ceiling side of the previously cut and

framed hole. See Figure 52. If the area above the ceiling is an attic,

position and secure the firestop on top of the previously framed

hole. See Figure 53.
NOTE:
Remove insulation from the framed area in the attic before

installing the firestop and/or vent pipes.

PIPE STRAP

STUD WALL

1” MIN.

(25.4mm)

FLUE OUTLET

48”

(1219mm)

FRAMING AND FINISHING

WALL FIRESTOP

HOLE IS OFF-SET

TOWARDS BOTTOM

OF WALL OPENING.

A

B

Vent Size

A

B

6 5/8"

10"

11"

8"

10 3/8" 12 3/8"