Product overview, About this product, Applicable models – Yaskawa BACnet MS/TP User Manual
Page 8: 2product overview
2
Product Overview
u
About this Product
The SI-B3 option connects an A1000 drives to a BACnet network and facilitates the exchange
of data.
This manual explains the handling, installation and specifications of this product. The SI-B3
option is a simple, networking solution that reduces the cost and time to wire and install factory
automation devices, while providing interchangeability of like components from multiple
vendors.
Drives can be monitored and controlled by a controller on a Building Automation and Control
network (BACnet) using RS-485 technology and MS/TP (Master-Slave/Token-Passing)
protocol. The drives conform to the BACnet application specific controller (B-ASC) device
profile.
Up to 127 drives can communicate on a single BACnet MS/TP network. If more drives or
BACnet devices are required, then a BACnet router is required to allow another MS/TP
network to be available with up to another 127 drives.
u
Applicable Models
The option can be used with the drive models in
.
Table 1 Applicable Models
Drive Series
Drive Model Number
Software Version
<1>
A1000
CIMR-Ao2Aoooo
VSA901017 and later
CIMR-Ao4A0002o
to 4A0675o
CIMR-Ao5Aoooo
VSA905045 and later
VSA901017 and later
<1>
See “PRG” on the drive nameplate for the software version number.
2 Product Overview
8
YASKAWA TOEP YEACOM 08A A1000 Option BACnet MS/TP SI-B3 Installation & Technical Manual