Analog output objects, Analog value objects, 10 bacnet objects supported – Yaskawa BACnet MS/TP User Manual
Page 35
u
Analog Output Objects
Table 13 Analog Output Objects
Object ID
Object Name
Modbus
Address
Precision
Range
Units
PV Access
AO1
Analog Output 1 Level
0007H
XXXX.X
0 to 100.0
%
C
AO2
Analog Output 2 Level
0008H
XXXX.X
0 to 100.0
%
C
u
Analog Value Objects
Table 14 Analog Value Objects
Object ID
Object Name
Modbus
Address
Precision
Range
Units
PV Access
AV1
Operation Cmd
0001H
XXXXX
0 to 65535
–
C
AV2
Frequency Cmd
0002H
XXX.XX
Depends on
o1-03
0.00 to
600.00
Hz
Depends on
o1-03
C
AV3
PI Setpoint Cmd
0006H
XXX.XX
0.00 to
100.00
%
C
AV4
MF Output 1 Cmd
0009H
XXXXX
0 to 255
–
C
AV5
Reference Select Cmd
000FH
XXXXX
–
–
C
AV6
Drive Status
0020H
XXXXX
–
–
R
AV7
Fault Details
0021H
XXXXX
–
–
R
AV8
Data Link Status
0022H
XXXXX
–
–
R
AV9
Frequency Reference
0040H
XXX.XX
Depends on
o1-03
–
Hz
Depends on
o1-03
R
AV10
Output Frequency
0041H
XXX.XX
Depends on
o1-03
–
Hz
Depends on
o1-03
R
AV11
Output Voltage
0045H
XXXX.X
–
Volts
R
AV12
Output Current
0026H
XXXX.X
–
Amps
R
AV13
Output Power
0047H
XXXX.X
(for drives
rated above
11 kVA)
XXX.XX
(for drives
rated 11
kVA or
lower)
–
kW
R
AV14
Torque Reference
0048H
XXXX.X
–
%
R
AV15
MF Input Status
002BH
XXXXX
–
–
R
10 BACnet Objects Supported
YASKAWA TOEP YEACOM 08A A1000 Option BACnet MS/TP SI-B3 Installation & Technical Manual
35