Analog input objects, 10 bacnet objects supported – Yaskawa BACnet MS/TP User Manual
Page 34

Property
Object Type
Device
Analog
Input
Analog
Output
Analog
Value
Binary
Input
Binary
Output
Binary
Value
ADPU_Timeout
Yes
–
–
–
–
–
–
Number_Of_ADPU_Retries
Yes
–
–
–
–
–
–
Max_Masters
Yes
–
–
–
–
–
–
Max_Info_Frames
Yes
–
–
–
–
–
–
Device_Address_Binding
Yes
–
–
–
–
–
–
Database_Revision
Yes
–
–
–
–
–
–
Present_Value
–
Yes
Yes
Yes
Yes
Yes
Yes
Status_Flags
–
Yes
Yes
Yes
Yes
Yes
Yes
Event_State
–
Yes
Yes
Yes
Yes
Yes
Yes
Reliability
–
Yes
Yes
Yes
Yes
Yes
Yes
Out_Of_Service
–
Yes
Yes
Yes
Yes
Yes
Yes
Units
–
Yes
Yes
Yes
–
–
–
Priority_Array
–
–
Yes
<1>
Yes
<1>
–
Yes
Yes
Relinquish_Default
–
–
Yes
<1>
Yes
<1>
–
Yes
Yes
Polarity
–
–
–
–
Yes
Yes
–
Inactive_Text
–
–
–
–
Yes
Yes
Yes
Active_Text
–
–
–
–
Yes
Yes
Yes
<1>
For Commandable Object Instances only.
u
Analog Input Objects
Table 12 Analog Input Objects
Object ID
Object Name
Modbus
Address
Precision
Range
Units
PV Access
AI1
Analog Input 1 Level
004EH
XXXX.X
–
%
R
AI2
Analog Input 2 Level
004FH
XXXX.X
–
%
R
AI3
Not Used AI3
–
–
–
–
–
AI4
Not Used AI4
–
–
–
–
–
AI5
Not Used AI5
–
–
–
–
–
AI6
Display Format o1-03
0502H
XXXXX
–
–
R
AI7
Scale Format b5-20
01E2H
XXXXX
–
–
R
AI8
Inverter Model o2-04
0508F
XXXXX
–
–
R
AI9
Rated Current n9-01
05D0H
XXXX.X
–
Amps
R
10 BACnet Objects Supported
34
YASKAWA TOEP YEACOM 08A A1000 Option BACnet MS/TP SI-B3 Installation & Technical Manual