Option led display, 4 option components – Yaskawa BACnet MS/TP User Manual
Page 11
u
Option LED Display
The option has four LEDs.
Two bi-color Status LEDs:
• Module status (MS) red/green
• Network status (NS) red/green
Two BACnet LEDs:
• Transmit (TX) green
• Receive (RX) green
The operational states of the option LEDs after completion of the BACnet power-up diagnostic
LED sequence are described in
. Wait at least 2 seconds for the power-up diagnostic
process to complete before verifying LED states.
Table 3 Option LED States
Name
Display
Operating Status
Remarks
Color
Status
MS
–
OFF
Power supply OFF
Power is not being supplied to the drive.
Green
ON
Normal operation
The option is operating normally and
initialization is complete.
Green
Flashing
Standby/Initializing
The option is in process of configuring or
waiting for configuration information.
Red
Flashing
Minor fault
The option has detected a recoverable
minor fault such as incomplete
configuration.
Red
ON
Major fault
The option has detected an unrecoverable
major fault.
Green/Red
Flashing
Option self-test
The option is in self-test mode.
NS
–
OFF
Power supply OFF
–
Green
ON
Connected
The device is currently communicating on
the network.
Green
Flashing
Not connected
The device currently is not communicating,
but is correctly configured. The state is
“waiting” for communication to resume.
Red
Flashing
Minor fault
A minor recoverable fault has occurred.
Red
ON
Major fault
A non-recoverable major network fault has
occurred.
Green/Red
Flashing
Network test
Power-up sequence and testing