BACnet

Workstation

Drive Drive Drive

MS/TP

BACnet over Ethernet

Router

Router

A1000

CIMR-AU5A0009FAA

600V 3Phase 5.5kW/3.7kW

A1000

CIMR-AU5A0009FAA

600V 3Phase 5.5kW/3.7kW

A1000

CIMR-AU5A0009FAA

600V 3Phase 5.5kW/3.7kW

Drive Drive Drive

MS/TP

A1000

CIMR-AU5A0009FAA

600V 3Phase 5.5kW/3.7kW

A1000

CIMR-AU5A0009FAA

600V 3Phase 5.5kW/3.7kW

A1000

CIMR-AU5A0009FAA

600V 3Phase 5.5kW/3.7kW

Figure 10 Connecting Multiple Drives to a BACnet Workstation – System Overview

The two ends of the BACnet network must be terminated with a 120 ohm resistor between

the “+” and “-” and signals. The SI-B3 has a built in termination resistor that can be enabled

or disabled using DIP switch S1. If a drive is located at the end of a network line, enable the

termination resistor by setting DIP switch S1 to the ON position. Disable the termination

resistor on all slaves that are not located at the end of the network line by setting DIP switch

S1 to the OFF position (The factory setting for DIP switch S1 is OFF).

5 Installation Procedure

YASKAWA TOEP YEACOM 08A A1000 Option BACnet MS/TP SI-B3 Installation & Technical Manual

21