Device object – Yaskawa BACnet MS/TP User Manual
Page 39

Object ID
Object Name
Modbus
Address
Active Text
Inactive
Text
PV Access
BV47
Modbus Comms Error
002CH:bit 14
ON
OFF
R
BV48
Modbus Timeout Error
002CH:bit 15
ON
OFF
R
BV49
CRC Error
003DH:bit 0
ON
OFF
R
BV50
Invalid Data Length
003DH:bit 1
ON
OFF
R
BV51
Parity Error
003DH:bit 3
ON
OFF
R
BV52
Overrun Error
003DH:bit 4
ON
OFF
R
BV53
Framing Error
003DH:bit 5
ON
OFF
R
BV54
Timeout Error
003DH:bit 6
ON
OFF
R
BV55
<1>
Parameter Accept
0910H:bit 0
ON
OFF
W
BV56
<1>
Parameter Enter
0900H:bit 0
ON
OFF
W
BV57
Drive Comms Error
-
ON
OFF
R
<1>
Refer to Accessing Drive Parameters and the Enter Command on page 40
for an explanation of how to read
and write drive parameters not listed in the analog or binary objects.
u
Device Object
The Device Object fully describes the BACnet device to the network. Notable is that the
Device Object Instance ID and the Device Object Name are configurable.
The Device Object Instance ID is a unique internetwork-wide numerical value. It is a 22-bit
value that can range from 0 to 4,194,303. It is configurable by parameters F6-48 and F6-49.
Any changes to these parameters will not take effect until the power is cycled to the drive.
The Device Object Name is a unique internetwork-wide character string. It is a 20-character
string. It is writable from the BACnet network. Any new string written will not take effect
until the power is cycled to the drive.
10 BACnet Objects Supported
YASKAWA TOEP YEACOM 08A A1000 Option BACnet MS/TP SI-B3 Installation & Technical Manual