8 troubleshooting – Yaskawa SI-EP3 PROFINET Installation User Manual
Page 48
8 Troubleshooting
48
YASKAWA TOEP YEACOM 07A 1000-Series Option PROFINET SI-EP3 Installation Manual
■
Option Fault Monitors U6-98 and U6-99
The option can declare error/warning conditions via drive monitor parameters on the drive
digital operator as shown in
Table 12 Option Fault Monitor Descriptions
Two drive monitor parameters, U6-98 and U6-99, assist in network troubleshooting:
• U6-98 displays the first declared fault since the last power cycle. U6-98 is only cleared
upon drive power-up.
• U6-99 displays the present option SI-EP3 status. U6-99 is cleared upon a network-issued
fault reset and upon
power-up.
If another fault occurs while the original fault is still active, parameter U6-98 retains the
original fault value and U6-99 stores the new fault status value.
Fault Condition
Fault Declared
Status Value
(U6-98/U6-99)
Description
No Fault
n/a
0
No faults.
Force Fault
EF0
3
Network sent a message to force this node to the fault
state.
Network Link
Down
BUS ERROR
1300
No network link to option board.
Network Failure
BUS ERROR
1301
Connection with PLC Timeout.
Default MAC
Address
None
1303
Factory default MAC Address programmed into the
option. Return for reprogramming.
No IP Address
None
1304
No IP Address has been programmed into the option.
No Station Name
None
1305
No Station Name has been programmed into the option.
Config Error
None
1306
Configuration error on power-up.
Init. Failure
None
1307
Initialize error on power-up.
Permanent
Communication
Loss
BUS ERROR
1308
Fatal error in MAC/PHY hardware, requires power cycle
to recover.