YASKAWA TOEP YEACOM 07A 1000-Series Option PROFINET SI-EP3 Installation Manual
6 Option Related Drive Parameters
6
Option Related Drive Parameters
The following parameters are used to set up the drive for operation with the option.
Parameter setting instructions can be found in the drive product manual.
Confirm proper setting of the all parameters in
before starting network
communications.
Table 6 Parameter Settings
No.
Name
Description
Default
b1-01
Frequency Reference
Selection
Selects the frequency reference input source.
0: Operator - Digital preset speed d1-01 to d1-17
1: Terminals - Analog input terminal A1 or A2
2: MEMOBUS/Modbus communications
3: Option PCB
4: Pulse Input (Terminal RP)
1
(Set to 3 for
PROFINET)
b1-02
Run Command
Selection
Selects the run command input source.
0: Digital Operator - RUN and STOP keys
1: Digital input terminals S1 to S7
2: MEMOBUS/Modbus communications
3: Option PCB
1
(Set to 3 for
PROFINET)
F6-01
Operation Selection
after Communications
Error
Determines drive response when a bUS error is detected
during communications with the option.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
4: Alarm (d1-04)
5: Alarm Ramp to Stop
1
F6-02
External Fault
Detection Conditions
(EF0)
Sets the condition for external fault detection (EF0).
0: Always detected
1: Detected only during operation
0
F6-03
Stopping Method for
External Fault from
Communication Option
Board
Determines drive response for external fault input (EF0)
detection during communication.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
1
F6-07
NetRef/ComRef
Selection Function
0: Multi-step speed reference disabled
1: Multi-step speed reference allowed
1
F6-08
Reset Communication
Related Parameters
Determines if communication-related parameters F6-
and F7- are set back to original default values when the
drive is initialized using parameter A1-03.
0: Do not reset F6- and F7- parameters
1: Reset F6- and F7- parameters
Note: Setting this parameter does not affect
communication-related parameters.
0