5 Installation Procedure
20
YASKAWA TOEP YEACOM 07A 1000-Series Option PROFINET SI-EP3 Installation Manual
■
Wiring the Option
5.
Route the option wiring.
Depending on the drive model, some drives may require routing the wiring through
the side of the front cover to the outside to provide adequate space for the wiring. In
these cases, using diagonal cutting pliers, cut out the perforated openings on the
left side of the drive front cover. Sharp edges along the cut out should be smoothed
down with a file or sand paper to prevent any damage to the wires.
5.a Route the PROFINET CAT 5e cable inside the enclosure for drives that do not
require routing through the front cover. Refer to
to determine the
proper wire routing by drive model.
Table 5 Model-Specific Cable Routing
Figure 7
Figure 7 Wire Routing Examples
Model CIMR-
Wire Routing
<1> Refer to
for examples of the different wire routing techniques.
Through Front
Cover
Inside Drive
2A0004 to 0040; 4A0002 to 0023; 5A0003 to 0011
(A)
-
2A0056 and above; 4A0031 and above; 5A0023 and above.
-
(B)
A – Route wires through the openings
provided on the left side of the
front cover.
<1> The drive will not meet NEMA Type 1 requirements if wiring is exposed outside the enclosure.
B – Use the open space provided
inside the drive to route option
wiring.
B
A